UPS runtime calculator

List the devices with their power in W, describe the battery bank and enter the UPS rating in VA and its power factor. The result is a linear runtime estimate, with battery current and UPS load. The prefilled values are examples: replace them with datasheet values and your own rack.

ups-runtime
Example values: replace them with measured or datasheet power. A single total such as 400 also works.
V
Ah
%
%
VA
More options
Wh
If filled in, replaces voltage × Ah × batteries.
Row of circuit breakers in an electrical panel
Row of circuit breakers in an electrical panel. Photo: Jason Leung / Unsplash

The math

A battery bank's energy is voltage times capacity. Batteries in series add voltage; strings in parallel add Ah. Only part of the nominal energy is used (the usable depth of discharge you enter) and the inverter loses another part in conversion (efficiency). Runtime is the remaining energy divided by the load:

bank Wh = V × Ah × batteries in series × strings in parallel
runtime (h) = Wh × usable depth of discharge × efficiency ÷ load (W)
battery current (A) = load ÷ (efficiency × bank voltage)
UPS load = load (W) ÷ (VA × power factor)

Step by step with the example values

The form starts with values that show the math: 4 devices adding up to 400 W, 4 batteries of 12 V and 9 Ah in series, 90% efficiency, 80% usable depth of discharge and a 1,500 VA UPS with a 0.9 power factor. They are not recommended or measured values of any product.

  1. Load: 120 + 40 + 60 + 180 = 400 W.
  2. Bank: 12 V × 4 = 48 V; 48 V × 9 Ah = 432 Wh.
  3. Usable: 432 × 80% = 345.6 Wh; at the inverter output, × 90% = 311.04 Wh.
  4. Runtime: 311.04 Wh ÷ 400 W = 0.778 h = 47 min.
  5. Battery current: 400 W ÷ (0.9 × 48 V) = 9.26 A.
  6. UPS: 1,500 VA × 0.9 = 1,350 W; 400 ÷ 1,350 = 29.6% load.

Table: the same bank at other loads

Example bank (432 Wh, 80% usable depth of discharge, 90% efficiency), linear math:

Load% of a 1,350 W UPSEstimated runtimeBattery current (48 V)
100 W7.41%3 h 7 min2.31 A
200 W14.8%1 h 33 min4.63 A
400 W29.6%47 min9.26 A
600 W44.4%31 min13.9 A
800 W59.3%23 min18.5 A
1,000 W74.1%19 min23.1 A
1,350 W100%14 min31.2 A

In the linear math, twice the load gives half the runtime. A real battery drops more than that, as explained below.

Why it is an estimate

  • Fast discharge: lead-acid batteries deliver less energy at high current (Peukert effect). The Ah on the label applies to the discharge rate the maker states in the datasheet (for example C20 = discharge over 20 hours). Runtimes of minutes fall below the linear math. The tool applies no Peukert exponent because it changes from battery to battery.
  • Age and temperature: capacity drops as the battery ages and changes with temperature.
  • End of discharge: the UPS shuts down at a minimum voltage it defines, which limits how much energy is used. That is what the usable depth of discharge field is for.
  • Efficiency: it changes with UPS load; the right value is in the model's datasheet.

Always check the result against the UPS manufacturer's runtime table, measured with its own batteries for each load. Use this math to compare scenarios and get the order of magnitude.

VA, W and power factor

A UPS has two limits: apparent power in VA and real power in W. Power in W is VA × power factor (PF). A 1,500 VA UPS with PF 0.9 delivers up to 1,350 W; with PF 0.6, up to 900 W. Rack load is added up in W, so the comparison is made in W. Above 100%, the load exceeds what the UPS supports. The tool also warns above 80%, the same 20% headroom used in the PoE calculator, because close to the limit there is little room for new equipment.

Battery current

The current drawn from the bank is the load divided by the bank voltage, corrected for efficiency. With 400 W, 48 V and 90%, that is 9.26 A. For the same load on a 24 V bank it would be 18.5 A. With the same Ah, higher current means faster discharge, and the Peukert effect weighs more.

How to get the load

Use measured consumption (on the UPS display, a metered PDU or a power meter) or the power stated in each device's datasheet. A power supply's rating is the maximum it can deliver, not its consumption: adding those values gives a ceiling estimate. A PoE switch also draws the power it delivers to cameras and access points; to add that part, use the PoE budget calculator.

Common mistakes

  • Treating VA as W: 1,500 VA with PF 0.9 is 1,350 W.
  • Adding the Ah of batteries in series: series adds voltage. 4 batteries of 12 V and 9 Ah in series give 48 V and 9 Ah (432 Wh), not 36 Ah.
  • Counting 100% of the energy and forgetting inverter efficiency and cut-off voltage.
  • Forgetting PoE in the switch load.
  • Trusting the linear math for a few minutes of runtime: in fast discharge the battery delivers less.

Frequently asked questions

How do I calculate UPS runtime?

Multiply the bank energy (V × Ah × batteries) by the usable depth of discharge and the efficiency, then divide by the load. Example: 432 Wh × 80% × 90% ÷ 400 W = 0.778 h, about 47 min. It is a linear estimate; check it against the manufacturer's runtime table.

Does doubling the batteries double the runtime?

In the linear math, yes: two strings of 4 batteries of 12 V and 9 Ah (864 Wh) give 1 h 33 min at 400 W, versus 47 min with one string. Since the current in each battery is halved, the fast-discharge loss also drops. Check whether the UPS accepts an external battery pack.

What is the difference between VA and W on a UPS?

W = VA × power factor. A 1,500 VA UPS with PF 0.9 supports 1,350 W; a 400 W load uses 29.6% of it.

Why is real runtime shorter than calculated?

Lead-acid batteries deliver less energy in fast discharge (Peukert effect), lose capacity with age and vary with temperature. The manufacturer's runtime table already accounts for how its batteries behave.

How much current comes out of the battery?

Load ÷ (efficiency × bank voltage). With 400 W, 90% and a 48 V bank: 9.26 A.

Study and design tool. Validate any configuration in a lab and against vendor documentation before applying it in production.